Fire doors are categorized by material into steel and wooden types; these two varieties differ slightly in installation methods and fire ratings, so attention to detail during installation is essential.
First, for wooden fire doors, the door frame dimensions should be 20 mm smaller than the rough opening, and the bottom of the frame should be embedded 20 mm into the floor. The frame must be securely anchored to the wall, ensuring it is plumb and square. Strict care must be taken regarding vertical alignment and squareness during frame positioning and bracing to avoid the need for planing or sawing later. There should be at least three fixing points on each side of the frame, with a spacing of no more than 800 mm.
Second, when installing steel fire doors, one must account for potential frame deformation; timber braces should be used to support the frame across its width, and the bottom of the frame should be embedded 20 mm into the floor before welding the frame to the wall's embedded anchors. Finally, an opening should be made in the wall near the top corner of the frame to pour in a concrete mixture of cement, sand, and expanded perlite (ratio 1:2:5); the door is ready for use once the concrete has set.